Select your language

SCHMIDT Flow Switch SS 20.200

Manufacturer: Schmidt
Product brochure (11/2023)
Instructions for use
3D-STP data
EU-Declaration of conformity (01/2024)
UK-Declaration of conformity (01/2024)

Thermal Flow Switch for monitoring of flow rate of air and gases.

  • Patented sensor head (dumb-bell head):

- Largely independent from flow direction

- Easy to clean (free of undercuts)

- Dirt-resistant

  • Probe length 100 … 500 mm
  • Measuring ranges 0 … 1 m/s to 0 … 20 m/s
  • Visual indication of switching and operating status
  • Potentiometer (pre-programmed as option)
  • Increased resistance to media with optional coating
  • Exhaust air monitoring system
  • Filter monitoring
  • Fume cupboards
  • Clean room and Pharma
  • Ventilation and Air conditioning
  • Semiconductor process equipment

Accessories

Connection technology

DescriptionArticle-Number
Power supply unit: output 24 V / 1A DC, supply voltage 115/230 V AC (strip terminal) 535 282

Mounting and fixing technology

DescriptionArticle-Number
Mounting flange, galvanized steel 301 048
Wall mounting flange, stainless steel, PTFE clamp ring 520 181
Compression fitting, stainless steel, G½, atmospheric pressure 532 160
Compression fitting, brass, G½, atmospheric pressure 517 206
Compression fitting, stainless steel, G½, max. 10 bar, with protection against pressure losses 524 919
Compression fitting, brass, G½, max. 10 bar, with protection against pressure losses 524 891
Welding sleeve, steel, G½, according to EN 10241, 5 pieces 524 916
Welding sleeve, stainless steel, G½, according to EN 10241, 2 pieces 524 882

Miscellaneous

DescriptionArticle-Number
Clip-on bars for protection of sensor head against mechanical impacts, stainless steel 531 026
Attachable 2-wires-clip for protection of sensor head against mechanical impacts, stainless steel, H2O2-resistant 559 124
Technical data
Measuring quantity Standard flow velocity wN based on standard conditions 1)
Measured medium Air or nitrogen, other gases on request
Measuring range wN 0 … 1 / 2.5 / 10 / 20 m/s
Lower detection limit wN 0.06 m/s
Threshold wN 5 … 95 % of measurement range (min. 0.1 m/s)
Threshold setting wN Potentiometer (270°)>br>Optionally pre-programmed by factory (potentiometer deactivated)
Measuring accuracy
Switching hysteresis wN ±5 % of threshold value; min. 0.1 m/s
Setting switching threshold wN Potentiometer (270°); optionally fix pre-programmed
Threshold pre-programmed wN ±3 % of measuring value + 0.1 m/s 2)
Response time (t90) wN 3 s (jump of wN from 0 to 5 m/s in air)
Switch-on delay 20 s
Temperature gradient wN < 2 K/min (at wN = 5 m/s in air)
Operating temperature
Sensor -20 … +85 °C
Electronics -20 … +70 °C
Storage temperature -20 … +85 °C
Material
Enclosure PBT (glass-fibre reinforced)
Sensor tube Stainless steel 1.4571
Sensor head PBT (glass-fibre reinforced), stainless steel 1.4571
Protective coating (optional) Polyurethane derivative
Sensor cable PVC
General data
Humidity Measuring mode: Non-condensing (< 95 % RH)
Operating pressure (max.) 0 … 10 bar (overpressure)
Display LED green: Operating status;
LED red: Switching status / sensor defective
Supply voltage 24 V DC ± 20 %
Current consumption Typical 40 mA (max. 70 mA, without signal current of relais output)
Switching output Semiconductor relais; max. 30 V / 100 mA / 300 mW RON,max = 25 Ω
Electrical connection Non-detachable cable, 4 wires, length 2 m, with ferrules
Maximum cable length 100 m max.
Mounting position Arbitrary
Minimum immersion depth 58 mm (< 58 mm on request)
Protection type Sensor probe: IP67; Enclosure: IP65 (with installed rubber plug)
Protection class III (SELV or PELV)
MTTF value (per 01.01.2011) > 50 years
Probe length L 100/200/350/500 mm
Weight Approx. 100 g (L = 350 mm)
Copyright MAXXmarketing GmbH